Question
Advertisements
Solution
We know that,
P=VI
I = `"P"/"V" = (5 xx 1000)/200` = 25A
Thus, safe limit of current through t he appliance is 25A and a fuse of rating BA cannot be used with an appliance of rating SkW, 200 v.