प्रश्न
1 MW power is to be delivered from a power station to a town 10 km away. One uses a pair of Cu wires of radius 0.5 cm for this purpose. Calculate the fraction of ohmic losses to power transmitted if
- power is transmitted at 220 V. Comment on the feasibility of doing this.
- a step-up transformer is used to boost the voltage to 11000 V, power transmitted, then a step-down transfomer is used to bring voltage to 220 V. (ρCu = 1.7 × 10–8 SI unit)
Advertisements
उत्तर
i. When power is transmitted at 220 V.
Power lost in transmission P = I2R
| P = VI |
P = 1 MV = 106 W
V = 220 Volt
`I = P/V = 1000000/220`
`I = 50000/11 A`
| R = `ρ I/A` |
⇒ R = `(ρl)/(pir^2)`
I = 10 km × 2 = 20,000 M
∴ A = πr2
r = 0.5 cm = 0.5 cm × 10–2 = 5 × 10–3 cm
ρCu = 1.7 × 10–8 Ωm
R = `(ρI)/A`
∴ R = `(1.7 xx 10^-8 xx 20,000)/(3.14 xx 5 xx 10^-3 xx 5 xx 10^-3)`
= `(170 xx 20000 xx 10^(-8+6))/(314 xx 5 xx 5)`
= `(170 xx 20000)/(314 xx 25 xx 100)` Ω
R = `(170 xx 800)/(314 xx 100) = (170 xx 4)/157 = 680/157` ≅ 4Ω
∴ Power loss = I2R
= `50000/11 xx 50000/11 xx 4 = (100 xx 10^8)/121 = 8.26 xx 10^7`
Power loss in heating = 82.6 MW
As 82.6 MW > 1 MW
So this method cannot be used to transmit the power.
ii. When power is transmitted at 11000 V
P = 106 W
VI = 1000000
11000 I = 1000000
`I = 1000000/11000 = 1000/11`
∴ RCu = 4Ω as already calculated in part (i)
∴ Power loss = P = I2R
P = `1000/11 xx 1000/11 xx 4 = 4000/121 xx 4^4`
P = `3.3 xx 10^4` Watt
Fractional power loss = `(3.3 xx 10^4)/10^6 = 3.3/1000` = 0.033
Power loss in 3.3%
APPEARS IN
संबंधित प्रश्न
State the principle of the step-down transformer and its working.
Express the turn ratio in terms of voltages.
The adjacent diagram shows a coil would around a soft iron bar XY. (a) State the polarity at the end X and Y as the switch is pressed. (b) Suggest one way increasing the strength of electromagnet so formed.

How are the e.m.f in the primary and secondary coils of a transformer related with the number of turns in these coils?
The secondary windings of a transformer in which the voltage is stepped down are usually made of thicker wire than the primary. Explain why.
What is the function of a transformer in an a.c. circuit? How do the input and output powers in a transformer compare?
The input and output voltages of a transformer are 220 V and 44V respectively. Find the current in input circuit if the output current is 2 A.
What is the function of a step-up transformer?
Copy the given diagram of a transformer and complete it. Name the parts A and B. Name the part you have drawn to complete the diagram. What is the material of this part? Is this transformer a step-up or step-down? Give reason.
Applying e.m. f to primary coil is 210 V. If the number of turns in primary coil is 200 turns and that of in secondary coil is 20 turns, then find out the output voltage. Name the type of transformer.
In a series resonant RLC circuit, the voltage across 100 Ω resistor is 40 V. The resonant frequency ω is 250 rad/s. If the value of C is 4 µF, then the voltage across L is
Which among the following, is not a cause for power loss in a transformer?
A transformer is essentially an a.c. device. It cannot work on d.c. It changes alternating voltages or currents. It does not affect the frequency of a.c. It is based on the phenomenon of mutual induction. A transformer essentially consists of two coils of insulated copper wire having different numbers of turns and wound on the same soft iron core.
The number of turns in the primary and secondary coils of an ideal transformer is 2000 and 50 respectively. The primary coil is connected to a main supply of 120 V and secondary coil is connected to a bulb of resistance 0.6 Ω.
The value of current in the bulb is ______.
A 60 W load is connected to the secondary of a transformer whose primary draws line voltage. If a current of 0.54 A flows in the load, what is the current in the primary coil? Comment on the type of transformer being used.
A transformer operating at primary voltage 8 kV and secondary voltage 160 V serves a load of 80 kW. Assuming the transformer to be ideal with purely resistive load and working on unity power factor, the loads in the primary and secondary circuit would be:
An ideal transformer converts 220 V a.c. to 3.3 kV a.c. to transmit a power of 4.4 kW. If primary coil has 600 turns, then alternating current in secondary coil is ______.
Two coils P and Q are kept near each other. When no current flows through coil P and current increase in coil Q at the rate 10A/s, the emf in coil P is 15mV. When coil Q carries no current and current of 1. 8A flows through coil P, the magnetic flux linked with the coil Q is ______.
Explain why core of a transformer is always laminated.