An appliance with a metal covering, rated at 2 kW, 220 V, is to be connected in a circuit. Given below are four diagrams (P, Q, R and S) depicting different circuit configurations.

- Identify the safest circuit.
- Write two reasons, supported by mathematical calculations, where applicable, to justify your choice.
Give Reasons
Justify
Numerical
Very Short Answer
Advertisements
Solution
Given, Power rating (P) = 2 KW = 2000 W
Voltage rating (V) = 220 V
a. The safest circuit is S.
b. There are two criteria for choosing circuit S:
- It is earthed so that in the case of a short circuit, all the excess current can flow to earth without harming the person.
- The current in the supply should be less than or equal to the current rating of the fuse.
Current in the circuit = `P/V`
= `2000/220`
= 9.09 A
Circuit P: As the circuit is not earthed, it is not safe.
Circuit Q:
- Circuit is earthed properly.
- Current in the circuit is 9.09 A but it has a fuse that has a current rating of 8 A so it will get damaged and hence someone can be hurt.
Circuit R:
- Because the circuit is not earthed properly, it is unsafe.
- Current in the circuit is 9.09 A and it has a fuse that has a current rating of 10 A.
Circuit S:
- Circuit is earthed properly.
- Current in the circuit is 9.09 A and it has a fuse that has a current rating of 10 A.
So circuit S satisfies all the necessary criteria for a safe circuit.