‘A fuse is rated 8 A’. can it be used with an electrical appliance of rating 5kW, 200V?
Advertisements
उत्तर
The safe limit of current which can flow through the electrical appliance is I = P/V = 5000/200
= 25 A; which is greater than 8 A. So, such fuse cannot be used.
संबंधित प्रश्न
Name the factors on which the heat produced in a wire depends when current is passed in it, and state how does it depend on the factors stated by you.
How is a fuse put in an electric circuit?
Describe with the aid of a diagram some form of a fuse which is used in the electric lighting circuit of a house. Give two reasons why a fuse must not be replaced by an ordinary copper wire.
Explain the meaning of the statement ‘the current rating of a fuse is 5 A’.
An electric kettle is rated 3 kW, 250 V. Give reason whether this kettle can be used in a circuit which contains a fuse of current rating 13 A.
(i) Write one advantage of connecting electrical appliances in parallel combination.
(ii) What characteristics should a fuse wire have ?
(iii) Which wire in a power circuit is connected to the metallic body of the appliance ?
How does the thickness of a fuse wire depend on its current rating?
What is the rating of fuse used in power circuits, in domestic use?
How does the length of a fuse wire depend on its current rating?
'A fuse is rated 8 A'. Can it be used with an electrical appliance of rating 5 kW, 200 V?