प्रश्न
A 3-pin mains plug is fitted to the cable for a 1 kW electric kettle to be used on a 250 V a.c. supply. Which of the following statement is not correct?
विकल्प
The fuse should be fitted in the live wire.
A 13 A fuse is the most appropriate value to use.
The neutral wire is coloured black.
The green wire should be connected to the earth pin.
Advertisements
उत्तर
A 13 A fuse is the most appropriate value to use.
Explanation:
Given: Power (P) = 1 kW
Voltage (V) = 250 V
We know that,
P = VI
⇒ I = `P/V`
⇒ I = `1000/250`
⇒ I = 4 A
A safety fuse rating should always be slightly higher than the device's normal operating current. For a device drawing 4 A, a 5 A fuse is the most appropriate. A 13 A fuse is way too high; it would allow dangerously high current to flow without blowing, failing to protect the circuit in a fault event.